Insulation/ PRACTICAL GUIDE

Ventilate an airtight home without losing control of heat

Separate required fresh air, local exhaust, infiltration and heat recovery.

THE FIRST THING TO KNOW

Air sealing and planned ventilation solve different problems: one limits uncontrolled leakage, while the other manages fresh air and pollutants.

1. Identify pollutants and moisture at their sources

List cooking, bathing, combustion, drying, cleaning and occupancy loads. Local exhaust is usually the direct response to a concentrated source; whole-house ventilation addresses the background requirement.

Do not use a single humidity or carbon-dioxide reading as a complete indoor-air-quality diagnosis. Sensors, locations and occupancy patterns all affect interpretation. Fuel-burning equipment requires combustion and carbon-monoxide safety checks.

DOE · Consumer guide to home ventilation

2. Define outdoor airflow before equipment

Determine the required outdoor-air rate from applicable local standards and the actual building. Record whether the system is supply-only, exhaust-only or balanced, and where air is intended to travel between rooms.

Measured fan airflow can differ from a label because ducts, filters and terminals add resistance. Provide commissioning points and access for cleaning rather than assuming installed flow equals catalogue flow.

3. Put ventilation into the heating calculation

Cold outdoor air creates a heating load proportional to airflow and temperature difference. The calculator uses a dry-air constant of 0.335 Wh per cubic metre-kelvin for a first estimate.

Heat-recovery equipment transfers sensible heat between exhaust and supply streams. DOE describes energy-recovery ventilation as controlled ventilation that reduces energy loss, but actual performance depends on airflow balance, frost control, leakage and operating conditions.

DOE Building Science · Energy recovery ventilation

4. Commission and maintain the air paths

Measure supply and exhaust flows, verify controls and check that local exhaust does not create unsafe pressure around combustion appliances. Document filter type, cleaning interval, condensate drainage and frost-mode behaviour.

Review the system after air-sealing work, equipment replacement or occupancy changes. A quiet fan is not proof of correct airflow, and a highly efficient heat exchanger cannot compensate for a blocked filter.

Keep four air quantities separate

QuantityHow it is establishedCommon confusion
Planned outdoor airStandard and designConfused with fan label
Measured supply/exhaustCommissioningAssumed from control setting
Local extractKitchen and bath operationCounted as continuous whole-house flow
Uncontrolled infiltrationBuilding leakage and weatherTreated as reliable ventilation

Worked example

Heating 120 m³/h of outdoor air

Indoor air is 21°C, outdoor air is −10°C and sensible recovery is assumed to be 75%.

No recovery = 0.335 × 120 × 31 = 1.25 kW
After recovery = 1.25 × (1 − 0.75) = 0.31 kW

This is a steady sensible-load estimate. Fan power, infiltration, humidity, defrost and part-load performance remain separate.

What to have ready

  • Applicable outdoor-air requirement
  • Measured supply and extract flows
  • Indoor and outdoor design temperatures
  • Recovery performance and frost-control data

Common mistakes

  • Using uncontrolled leaks as a ventilation plan.
  • Assuming labelled and installed airflow are identical.
  • Ignoring filters, condensate and frost modes.

USE THE NUMBERS

Related calculators

Keep going

Reference check: 5 September 2026. Sources include US public agencies. Principles are general; regulations and design values must be checked where you live.Worked examples use stated hypothetical inputs.