Electrical power/ CALCULATOR
DC cable area for a voltage-drop target
Estimate the copper conductor area needed to keep steady DC voltage drop below a chosen percentage.
0.96 V
14.58 mm²
16.0 mm²
0.88 V
1.82 %
70.0 W
Interpretation:Voltage drop alone requires at least 14.58 mm²; the next area in this screening list is 16 mm², with about 1.82% drop and 70 W of cable heat. Verify ampacity, protection and installation rules separately.
Copper resistivity 0.0175 Ω·mm²/m at a reference temperature, equal outgoing and return conductors, steady DC current and a generic metric area list. Temperature, connection resistance, conductor ampacity, insulation, bundling, terminals, fuses, fault current and local rules are excluded. The listed area is a voltage-drop screen, never a complete cable selection.
Continue your calculation
DC cable voltage drop
Estimate copper-cable voltage drop, percentage loss and heat at a steady current.
Inverter DC input current
Convert an AC load and inverter efficiency into approximate battery-side power and current.
Battery runtime from a steady load
Estimate ideal runtime from nominal energy, usable fraction, inverter efficiency and load.
Inverter running and motor-start screen
Compare one documented motor start plus other loads with derated continuous and surge inverter ratings.